Eurobatex Class 0 Pipe Insulation |
|
|
|
 |
|
PHYSICAL
PROPERTIES
|
TECHNICAL
DATA
|
TEST
METHOD
|
CERTIFICATION AND
SUPERVISION BOARD
|
|
Operating temperature
max. temperature of the fluid handled
min. temperature of the fluid handled
|
+ 105 °C
- 45 °C
|
|
|
|
Thermal conductivity l
At meav
temperature indicated
- 40°C
- 30°C
- 20°C
- 10°C
- 0°C
+ 10°C
+ 20°C
+ 30°C
+ 40°C
+ 50°C
|
0,028 W/(m·K)
0,029 W(m·K)
0,030 W(m·K)
0,032 W(m·K)
0,033 W(m·K)
0,034 W(m·K)
0,036 W(m·K)
0,038 W(m·K)
0,039 W(m·K)
0,040 W(m·K)
|
DIN 52613
|
Istituto
Giordano
Bellaria (FO)
Fachlaboratorium für
Permeationspüfung
Wiesbaden
(Germany)
|
|
Permeability
Water vapour diffusion resistance
µ factor
|
7000
|
DIN 52615
|
FIW - Munich and factory test
|
|
Fire rating
Italy
U.K.
France
Sweden
Norway
Finland
Switzerland
Austria
|
Classe 1
I 12.0i1 6.0
Class 1
Class M1
Klass II
Klass II
Klass II
Klass I
ISO 834/1975
BKZ 5,2
Klasse B1
Schwerbrennbar
|
UNI 9174 - UNI 8457
BS 476 Part. 6:1989
BS 476 Part 7: 1997
AFNOR NF P92 501
NT F 036
NT F 036
NT F 036
NT F 002
EN 1336/1998 Part 3
-
ÖNORM B 3800 TI
UNI 4905
|
Ministry of the Interior Approval
n. for every single thickness
Warrington Fire Research Institute.
Achieves Class 0 as defined in U.K.
Building Regulations.
LNE - France
SP Boras - Sitac
SP Boras - Sitac
SP Boras - Finnish Ministry of
Environment
EMPA - Bern
ÖKI-Österreichisches
Kunstoffinstitut Wien
|
|
Ozone resistance
|
Excellent
|
UNI 4905
|
Cernise -
Milano
|
|
Dimensional stability
at + 105 °C
at - 45 °C
|
0,3% shrinkage
0,5% shrinkage
|
|
Factory
test
|
|
 |
|
|
|
|